The Soeteck room-level liquid cooling solution is built around large coolant distribution units (CDUs) that serve an entire data hall of cold-plate liquid-cooled servers. A plate heat exchanger separates the facility cooling-water loop from the secondary technology loop, delivering conditioned coolant to the racks while keeping the two circuits isolated.
It is aimed at medium-to-large liquid-cooled data centres with 100 or more liquid-cooled racks, HPC clusters running CPU- and GPU-intensive workloads such as weather simulation and genome sequencing, and AI computing centres training large models on big GPU clusters.
The SY-CDU-RM range covers 1,000, 1,350 and 2,000 kW of heat exchange. On the primary side, cooling water enters at 35 °C and leaves at 45 °C; the secondary side circulates 25% ethylene glycol supplied at 40 °C and returned at 50 °C, with at least 120 kPa of available head for the rack manifolds. The source documentation also cites a solution range of up to 2,500 kW.
ServerInvest sizes, supplies and integrates room-level CDUs with liquid-cooled Supermicro GPU servers, racks, manifolds and power, and the full hall can be planned in our 3D Room Builder.
Key features
Every configuration is reviewed for compatibility, power and thermals before we confirm your order.
48 hours of CPU, memory and storage stress testing, with a test report shipped in the box.
Rails, labelled cables and your OS pre-installed — unbox, rack and power on.